Manostar Switch MS61A: Small Differential Pressure Switch
UL Approved

Model |
High Limit, Vinyl Tubing |
Low Limit, Vinyl Tubing |
|
MS61A HV |
MS61A |
|
|
Units Type of Measurement Mechanism Gases Measured Pressure Measurement Installation Operating Temperature Operating Humidity Maximum Pressure Outer Casing Shock Resistance Vibration Resistance Insulation Resistance Electrical Resistance Applicable Tubing Connector Orientation of Connector Weight Accessories |
Pa, kPa Differential
Pressure Diaphragm Air and non-corrosive gases (no liquids) Adjusted by knob with indicator Free position: horizontal-vertical -10‹C~50‹C (no icing) Less than90%RH (no condensation) 100kPa Polyamide 5-10Hz Total
Amplitude 10mm 10 50Hz
Accelerated Amplitude 39m/s2 (2 hours in each triaxial
direction) 100m/s2
(6 times in each triaxial direction) Terminal to case:
20MW+ (500V
DC megger) Terminal to case:
1500V AC 50/60 Hz 1 min. Soft PVC or
rubber tubing (internal diameter 4 mm) Built-in High pressure
side marked gHh, low pressure side marked gLh Approx. 140g VT4-6 vinyl
tubing Approx. 1m (ID 4 mmx OD 6 mm) |
|
|
Range Code |
|
Accuracy (20‹C) |
Maximum Pressure Differential |
Diaphragm Material |
Diaphragm Pressure Resistance |
|
120D |
20~120 Pa |
} 5 Pa |
25 Pa |
Silicon
Rubber |
20kPa |
|
300D |
50~300 Pa |
} 15 Pa |
40 Pa |
||
|
600D |
100~600 Pa |
} 25 Pa |
80 Pa |
||
|
1.2E |
0.2~1.2 kPa |
} 50 Pa |
160 Pa |
||
|
3E |
0.5~3 kPa |
} 150 Pa |
400 Pa |
||
|
6E |
1~6 kPa |
} 300 Pa |
800 Pa |
·
If you are planning to install the
gauge facing downward (horizontally, or at an angle), please specify
at the time of order, as the unit must be adjusted prior to shipment.
·
When measuring flammable gases, or
using switch in a flammable atmosphere, use anti-explosive construction and
contact signal exchangers.
|
General Load |
Silver
Contact Micro Switch |
Rated
Voltage |
Resistive
Load |
Inductive
Load |
Load on
Motor |
|
Contact
construction: Electrical
life: over 100,000 cycles Contact
material: pure silver (circular rivet points) |
30V DC |
3A |
2A |
----- |
|
|
125V AC 250V AC |
5A 5A |
3A 3A |
1A 0.5A |
||
|
Low
Load |
Gold
Contact Micro Switch |
Rated
Voltage |
Resistive
Load |
Inductive
Load |
Load on
Motor |
|
Contact
construction: SPDT (single pole double
throw) Electrical
life: over 100,000 cycles Contact material: gold alloy (cross points) |
30V DC |
0.1A |
---- |
---- |
|
|
125V AC |
0.1A |
---- |
---- |
·
Reliability
of the general load contact is reduced when used with very low voltage or
current; the low load model should be used in such cases.
·
Always
use surge protection circuits to prevent contact damage when using inductive
load circuits such as relays.
For more information, please contact:
Mihama Corporation
E-mail: info@ mihama.com
Tel: +81-3-4570-3800
Fax: +81-3-4570-3803