Manostar Switch IBRC: Intrinsically Safe Construction Contact Signal Converter

 

 

 

Model

IBRC6011R-1

IBRC6012R-1

IBRC6021R-1

IBRC6022R-1

# of Circuits

1

2

Power Supply Voltage

AC100/110V

AC200/220V

AC100/110V

AC200/220V

Explosion-proofing

Protective Construction

Applicable Gas

Installation Points

 

 

Voltage Resistance

 

 

 

Insulation Resistance

Operating Temperature

Operating Humidity

Weight

Intrinsically-safe construction

Body: IP40 (Terminal: IP20)

 

3nG5

Non-hazardous sealed container

Hazardous point connected to safe circuit at contact points Class 0 – Class 2

Btw. safe and non-safe circuit:: AC 1500V 1 min

Btw. safe circuit & metal ground: AC 500V 1 min

Btw. non-safe circuit & metal ground:
AC1500V 1min

Over 100MW (500V DC megger)

-10°C~50°C (no icing)

 

45~85%RH (no condensation)

1-circuit: 400g,  2-circuit: 450g

Intrinsically Safe Circuit (input side)

 

 

 

 

 

 

 

Non-intrinsically Safe Circuit (output side)

Hazardous point of contact: Non-voltage
contact with protective construction in excess of
total enclosure.

Rated open-circuit voltage: DC16V

Rated current:: 14 mA

External wire conditions:

Inductance less than 1.7mH

Capacitance less than 72nF

Resistance less than 600W/n+1

Relay Output

Contact construction:  1a

Maximum contact current: AC250V, DC60V

Maximum current: 5A

Rated load:  AC110V/DC24V 5A

AC220V 2.5A (resistive load)

 

                                                                                                                                                                                                            

For more information, please contact:

Mihama Corporation                                     E-mail: info@ mihama.com

1-2-8 Toranomon, Minato-ku

Tokyo 105-8437  Japan
Tel: +81-3-4570-3800 

Fax: +81-3-4570-3803