Manosys Receiver: EMP2·EMP3

 

 

 

Model

EMP2

EMP3

Display

Input Signal

 

Output Signal

 

 

Output Signal

Accuracy

Power Supply

Digital 3 1/2 digit

4~20mA DC (Input resistance 250W) Full-scale value may vary in the case of airflow measurement.

2-wire type direct current power supply for use with pressure transmitter: 24V DC non-internal, or

4~20mA DC (load resistance less than 500W)

In the case of airflow measurement, input signal is the extracted square root of the output signal.

Within ± 1%F.S. (at 20°C) For airflow measurement: 15-100%F.S extracted output value only.

 

100V AC ± 10% 50/60 Hz  EMP2 about 7VA, EMP3 about 6VA

Alarm

(Relay Contact

 Output)

2 circuits (one at upper and lower limits)

None

Outer Casing

Operating Temp.

Operating Humidity

Insulation Resistance

Voltage Resistance

Accessories

ABS resin (ivory)

0°C~50°C (no icing)

90%RH or less (no condensation)

 

Terminal to case: over 20MW (500V DC megger)

 

Terminal to case:  1500V AC 50/60Hz 1 min

 

Installation fittings (2)

Weight

Approx. 650g

Approx. 500g


 

Pressure Range

Code

Pressure Range

Accuracy at 20°C

Temp. Drift
(0~40
°C)

Alarm

 

D10

D20

D30

D50

D100

D200

D300

D500

D1000

0~10 Pa

0~20 Pa

0~30 Pa

0~50 Pa

0~100 Pa

0~200 Pa

0~300 Pa

0~500 Pa

0~1 kPa

Up to

±1%F.S.

± 1 digit

 

For airflow measurement: 15-100% F.S

Up to ±0.05%F.S/°C.

Form of output:

2xSPDT

(one circuit at upper and lower limits)

 

Contact Capacity:

MAX. 1.5A 120V AC

1.5A 30V DC

MIN.   0.1A 5V DC

 

Range of Settings:

Upper Limit: 15-100%F.S.

Lower Limit: 0-85%F.S.

 

On-Off Dead band:

Within 2% F.S.

E2

E3

E5

E10

E20

E30

E50

0~2 kPa

0~3 kPa

0~5 kPa

0~10 kPa

0~20 kPa

0~30 kPa

0~50 kPa

D ± 10

D ± 20

D ± 30

D ± 50

D ± 100

D ± 200

D ± 300

D ± 500

D ± 1000

± 10Pa

± 20Pa

± 30Pa

± 50Pa

± 100Pa

± 200Pa

± 300Pa

± 500Pa

± 1000Pa

 

E ± 2

E ± 3

E ± 5

± 2 kPa

± 3 kPa

± 5 kPa

 

Airflow Range Code

Airflow Range

(Note 1)

 

None

0~A B C

 

Note 1:v A: Value (rounded off),  B: Multiplying power (x10, x100, x1000, x10000),

C: Unit (m3/h, m3/min, Nm3/h, Nm3/min)

·              Negative displays (such as 0~ -100Pa) are also available.

                                                                                                                                                            